Manufacturer: Eaton Powerware
Model: Eaton Powerware 9130 3000VA 2700W, RM, 2U, 30A, 120V, New Batteries, Refurbished UPS
Condition: New batteries, refurbished UPS
Part Number: PW9130L3000R-XL2U
Maximum output: 2700W / 3000VA
Typical backup time at half load: 13 minutes (1350 Watts)
Typical backup time at full load: 5 minutes (2700 Watts)
Warranty: 1 year full replacement warranty
Eaton Powerware 9130 3000VA 2700W PW9130L3000R-XL2U - User Manual
General:
Topology
Online (Double Conversion)
Configuration
Rackmount
Catalog Number
PW9130L3000R-XL2U
Color
Black
Rating (VA/Watts)
3000/2700
Diagnostics
Full system self-test
UPS Bypass
Automatic bypass
Dimensions (H x W x D, inches)
3.4 x 17.2 x 23.6
Weight (lbs)
65
Rail Kit Included
Included with all rackmount units
Remote Emergency Power off (REPO)
Emergency shutdown control through the REPO port
Efficiency
>95% in high-efficiency mode; >86% in online mode
Input:
Connection
NEMA L5-30P
Input Cord
6 ft.
Input Voltage Range
90-144 VAC
Nominal Voltage
120V default (100/110/120/127V)
Frequency
50/60 Hz
Frequency Range
45–65 Hz
Nominal Current
25 A
Breaker Ratings
30A
Output:
Nominal Voltage
120V default (100/110/120/127V)
Output Receptacles
(6) NEMA 5-20R
(1) NEMA L5-30R
On Utility Voltage Regulation
±3% of nominal
On Battery Voltage Regulation
±3% of nominal
Power Factor
0.9
Frequency Regulation
±3% Hz online
Load Crest Factor
3 to 1
Battery:
Optional Extended Battery Module
PW9130N3000R-EBM2U
Maximum number of extended battery modules (EBM)
4
Battery Management
ABM technology
Battery Type
72 Vdc; (6) 12V, 9 Ah. Hot-swappable internal and external batteries.
Battery Replacement
EBP-1607
Start On Battery
Allows start of UPS without utility input
Recharge Time
Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours
Communications:
User Interface
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish
LEDs
Four status-indicating LEDs
Communication Ports
(1) USB, (1) RS-232 serial, Relay output (common alarm standard)
Communication Slot
Optional communication slots (BD Slot)
Power Management Software
Bundled software suite CD
Environmental & Standards:
RoHS Compliance
Yes
Heat Dissipation (BTU)
Line: 1257, Bat: 1755
Audible Noise
<50 dB
Operating Temperature
0°C to 40°C (32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating
Safety markings
UL, cUL, VCCI
EMC Markings
FCC Class A, EN55022 Class A
Storage Temperature
-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131°F) without batteries
Relative Humidity
5–90% non-condensing